.. _drivers:
=================
Enabling Drivers
=================
DRAC
----
DRAC with PXE deploy
^^^^^^^^^^^^^^^^^^^^
- Add ``pxe_drac`` to the list of ``enabled_drivers in`` ``/etc/ironic/ironic.conf``
- Install openwsman-python package
SNMP
----
The SNMP power driver enables control of power distribution units of the type
frequently found in data centre racks. PDUs frequently have a management
ethernet interface and SNMP support enabling control of the power outlets.
The SNMP power driver works with the PXE driver for network deployment and
network-configured boot.
Supported PDUs
^^^^^^^^^^^^^^
- American Power Conversion (APC)
- CyberPower (implemented according to MIB spec but not tested on hardware)
- EatonPower (implemented according to MIB spec but not tested on hardware)
- Teltronix
Software Requirements
^^^^^^^^^^^^^^^^^^^^^
- The PySNMP package must be installed, variously referred to as ``pysnmp``
or ``python-pysnmp``
Enabling the SNMP Power Driver
^^^^^^^^^^^^^^^^^^^^^^^^^^^^^^
- Add ``pxe_snmp`` to the list of ``enabled_drivers`` in ``/etc/ironic/ironic.conf``
- Ironic Conductor must be restarted for the new driver to be loaded.
Ironic Node Configuration
^^^^^^^^^^^^^^^^^^^^^^^^^
Nodes are configured for SNMP control by setting the Ironic node object's
``driver`` property to be ``pxe_snmp``. Further configuration values are
added to ``driver_info``:
- ``snmp_address``: the IPv4 address of the PDU controlling this node.
- ``snmp_port``: (optional) A non-standard UDP port to use for SNMP operations.
If not specified, the default port (161) is used.
- ``snmp_outlet``: The power outlet on the PDU (1-based indexing).
- ``snmp_protocol``: (optional) SNMP protocol version
(permitted values ``1``, ``2c`` or ``3``). If not specified, SNMPv1 is chosen.
- ``snmp_community``: (Required for SNMPv1 and SNMPv2c) SNMP community
parameter for reads and writes to the PDU.
- ``snmp_security``: (Required for SNMPv3) SNMP security string.
PDU Configuration
^^^^^^^^^^^^^^^^^
This version of the SNMP power driver does not support handling
PDU authentication credentials. When using SNMPv3, the PDU must be
configured for ``NoAuthentication`` and ``NoEncryption``. The
security name is used analagously to the SNMP community in early
SNMP versions.
iLO driver
----------
.. toctree::
:maxdepth: 1
../drivers/ilo
SeaMicro driver
---------------
.. toctree::
:maxdepth: 1
../drivers/seamicro