Outlet Temperature Based Strategy
|
||||
==========================================
|
||||
|
||||
https://blueprints.launchpad.net/watcher/+spec/outlet-temperature-based-strategy
|
||||
|
||||
Outlet(Exhaust Air) temperature is a new thermal telemetry which can be used
|
||||
to measure the server's thermal/workload status.
|
||||
|
||||
This spec proposes a new Watcher migration strategy based on the outlet
|
||||
temperature of servers. This strategy makes decisions to migrate workloads
|
||||
to the servers with good thermal condition (lowest outlet temperature) when
|
||||
the outlet temperature of source servers reach a configurable threshold.
|
||||
|
||||
Note: "server" in this document means "hypervisor".
|
||||
|
||||
Problem description
|
||||
===================
|
||||
|
||||
In current Data Center infrastructure, the cooling air supply to servers can
|
||||
be different. When a server is overloaded or the supply air is too hot, the
|
||||
outlet temperature telemetry can be used to detect the problem. In order to
|
||||
have the server in a reliable thermal condition, some of the server's
|
||||
workloads should be migrated to other server with safer thermal conditions.
|
||||
|
||||
Use Cases
|
||||
----------
|
||||
|
||||
As an administrator, I want to be able to trigger an audit that controls the
|
||||
temperature and perform workload load balancing.
|
||||
|
||||
In order to :
|
||||
|
||||
* Reduce the total power consumption spent on cooling.
|
||||
|
||||
* Increase the lifespan of the data center because cooling effectiveness is a
|
||||
first order factor.
|
||||
|
||||
Project Priority
|
||||
-----------------
|
||||
|
||||
Not relevant because Watcher is not in the big tent so far.
|
||||
|
||||
Proposed change
|
||||
===============
|
||||
|
||||
Watcher already has its decision framework, so this strategy should be a new
|
||||
class which extend the base strategy class.
|
||||
|
||||
* Set the threshold in 2 steps : hard coded first, then through the template.
|
||||
|
||||
* Create a new Python class to extend the "BaseStrategy" class.
|
||||
|
||||
* Use the Ceilometer client to get Outlet temperature metrics of hypervisors.
|
||||
|
||||
* Use the Nova objects framework to get free CPU/Memory/Disk of hypervisors.
|
||||
|
||||
* An algorithm to detect if the threshold of Outlet temperature has been
|
||||
reached and to choose the migration target server. It will filter the viable
|
||||
targets according to the free resource information of hypervisors from
|
||||
previous step.
|
||||
|
||||
|
||||
Alternatives
|
||||
------------
|
||||
|
||||
No alternative
|
||||
|
||||
Data model impact
|
||||
-----------------
|
||||
|
||||
None
|
||||
|
||||
REST API impact
|
||||
---------------
|
||||
|
||||
None
|
||||
|
||||
Security impact
|
||||
---------------
|
||||
|
||||
None
|
||||
|
||||
Notifications impact
|
||||
--------------------
|
||||
|
||||
None
|
||||
|
||||
Other end user impact
|
||||
---------------------
|
||||
|
||||
None
|
||||
|
||||
Performance Impact
|
||||
------------------
|
||||
|
||||
There used to be some performance issues regarding the query of metrics from
|
||||
the Ceilometer database. This is one of the reason why it was rarely used in
|
||||
production environment. These issues may now be solved thanks to an
|
||||
abstraction layer which enables anybody to change the underlying metrics
|
||||
storage backend easily.
|
||||
There is also a performance issue when you query the Nova DB to get cpu
|
||||
usage metrics.
|
||||
|
||||
Other deployer impact
|
||||
---------------------
|
||||
|
||||
None
|
||||
|
||||
Developer impact
|
||||
----------------
|
||||
|
||||
None
|
||||
|
||||
|
||||
Implementation
|
||||
==============
|
||||
|
||||
Assignee(s)
|
||||
-----------
|
||||
|
||||
Primary assignee:
|
||||
<junjie-huang>
|
||||
|
||||
|
||||
Work Items
|
||||
----------
|
||||
|
||||
1. function to use Ceilometer client to get outlet temperature of hypervisors.
|
||||
|
||||
2. function to filter servers by Nova basic metrics(free CPU/Memory/Disk)
|
||||
|
||||
3. Rewrite execute function to add the algorithm to detect if the threshold
|
||||
of outlet T has been reached and choose the target hypervisor, generate
|
||||
action plan.
|
||||
|
||||
|
||||
Dependencies
|
||||
============
|
||||
|
||||
* https://wiki.openstack.org/wiki/Ceilometer/blueprints/APIv2
|
||||
|
||||
* https://blueprints.launchpad.net/ceilometer/+spec/api-v2-improvement
|
||||
|
||||
* http://docs.openstack.org/admin-guide-cloud/telemetry-measurements.html
|
||||
|
||||
* http://docs.openstack.org/developer/python-novaclient/api.html
|
||||
|
||||
|
||||
Testing
|
||||
=======
|
||||
|
||||
Unit tests and functional test, will use a fake metrics set for running
|
||||
functional test.
|
||||
|
||||
|
||||
Documentation Impact
|
||||
====================
|
||||
|
||||
A documentation explaining how to use this new optimization strategy.
|
||||
|
||||
|
||||
References
|
||||
==========
|
||||
|
||||
http://www.intel.com/content/www/us/en/servers/ipmi/ipmi-home.html
|
||||
|
||||
|
||||
History
|
||||
=======
|
||||
|
||||
None
|