Install PTP Notifications
notification is packaged as a system application and is managed using
the system application
and system helm-override
commands.
The application monitors time related services on a host and provides an API for subscribing to asynchronous status notifications as well as the ability to pull the state of each service on demand.
Note
Changes to a node's configuration, applied using the system ptp-instance-apply
, requires the
ptp-notification
application to be removed and reapplied,
using the system application-remove ptp-notification
, and
system application-apply ptp-notification
commands. This allows the containers to reload the updated configuration
files and monitor the services correctly.
v1 API
The legacy functionality of ptp-notification
remains
available and is accessible through the v1 API; v1 is only capable of
reporting status changes for the Sync State on a system.
Limitations
The v1 API only supports monitoring a single
ptp4l + phc2sys
instance. Ensure the system is not
configured with multiple instances when using the v1 API.
v2 API
The API conforms to O-RAN.WG6.O-Cloud Notification API-v02.01. Using
the v2 API, multiple ptp4l
instances can be tracked for
independent Sync State and Clock Class notifications.
The application monitors the following services:
- PTP Sync State
- PTP Clock Class
- OS Clock Sync State
- GNSS Sync State
- Overall System Sync State
provides the capability for application(s) to subscribe to asynchronous status notifications and pull for the state on demand.
You must provide Helm override values indicating the
ptp4l
and phc2sys
instances that you want
tracked by your ptp-notification
application.
Since multiple ptp4l
instances can be supported on a
node, you must specify the ServiceName
of the instance that
the ptp-notification
application should track.
For example, follow the steps below:
Apply labels to nodes that will be running the
ptp-notification
.Apply the registration label to the controller nodes.
~(keystone_admin)]$ system host-label-assign controller-0 ptp-registration=true
Apply the notification label to each node that is configured for PTP clock synchronization.
~(keystone_admin)]$ system host-label-assign controller-0 ptp-notification=true ~(keystone_admin)]$ system host-label-assign compute-0 ptp-notification=true
Verify the labels.
~(keystone_admin)]$ system host-label-list <node name>
Locate the application tarball on the system controller.
~(keystone_admin)]$ ls /usr/local/share/applications/helm/ptp-notification-<version>.tgz
Upload the
ptp-notification
application using the command below.~(keystone_admin)]$ system application-upload <path to application>
Verify if the application is in the uploaded state.
~(keystone_admin)]$ system application-list
Apply Helm overrides as required. Create a yaml file and update the fields that require Helm overrides.
~(keystone_admin)]$ system helm-override-update ptp-notification ptp-notification notification --values notification-override.yaml
Note
You can override the default values for the
ptp-notification
application either by creating separate override sections for v1 and v2 APIs or by including v1 and v2 APIs in a single file as shown in the example below.~(keystone_admin)]$ cat notification-override.yaml ptptracking: ptp4lServiceName: ptp4l-legacy phc2sysServiceName: phc2sys-legacy logging_level: INFO ptp4lClockClassLockedList: "6,7,135" device: holdover_seconds: 15 poll_freq_seconds: 2 ptptrackingv2: ptp4lServiceName: True phc2sysServiceName: True ts2phcServiceName: True ptp4lClockClassLockedList: "6,7,135" phc2sysToleranceThreshold: 1000 log_level: INFO control_timeout: 2 device: holdover_seconds: 15 osclock: holdover_seconds: 15 overall: holdover_seconds: 15
To configure the
ptp-notification
v1 API in a seperate section, include the following in thenotification-override.yaml
file. Ensure that values are updated to match the configured instance names on your system.ptptracking: enabled: True ptp4lSocket: /var/run/ptp4l-instancename ptp4lServiceName: ptp4l-instancename phc2sysServiceName: phc2sys-instancename logging_level: INFO ptp4lClockClassLockedList: "6,7,135" device: holdover_seconds: 15 poll_freq_seconds: 2
ptptracking
where the values are:
ptp4lSocket
-
Update this value to include the correct instance name of your configured ptp4l instance.
ptp4lServiceName
-
Update this value to the instance name of your configured ptp4l instance.
phc2sysServiceName
-
Update this value to the instance name of your configure phc2sys instance.
logging_level: INFO
-
Set the logging level. DEBUG can be used for additional logs.
ptp4lClockClassLockedList
-
Set the list of clock classes that will allow
ptp-notification
to report Locked. The clockClass for a monitored ptp4l instance is read via the . If the instance clockClass matches one of theptp4lClockClassLockedList
values, thenptp-notification
will report Locked for that instance.The default values are "6,7,135", which means that
ptp-notification
will report locked when reading a clockClass of 6, 7 or 135 from the configured ptp4l instance. These values are recommended for nodes operating as Boundary Clock (BC).For nodes operating as , it is recommended to set the value to "6", so that only clockClass 6 is reported as locked.
holdover_seconds
-
holdover_seconds
configures how long each service will stay in the HOLDOVER state before transitioning to FREERUN. The holdover value used by the application equates to: holdover_seconds -(poll_freq_seconds * 2).This is done in order to account for time between the monitor polling cycles. The
holdover_seconds
value should be configured to match the validated holdover time provided by the device manufacturer. poll_freq_seconds
-
poll_freq_seconds
sets how frequently, in seconds the services are checked.
To configure the
ptp-notification
v2 API in a separate section, include the following in thenotification-override.yaml
file. Ensure that values are updated to match the configured instance names on your system.ptptrackingv2: ptp4lServiceName: True phc2sysServiceName: True ts2phcServiceName: True log_level: INFO ptp4lClockClassLockedList: "6,7,135" phc2sysToleranceThreshold: 1000 control_timeout: 2 device: holdover_seconds: 15 osclock: holdover_seconds: 15 overall: holdover_seconds: 15
ptptrackingv2
where the values are:
ptp4lServiceName: True
phc2sysServiceName: True
ts2phcServiceName: True
-
- The ServiceName fields are defaulted to "True" in the application and do not need to be altered.
- A service can be set to "False" in order to disable tracking for that type. However, if a service type is not configured on the node (i.e. node does not use ts2phc), then the application automatically determines this and does not attempt to monitor the node.
- Use these fields if there is a service that is configured on the node that you do NOT want to track.
log_level: INFO
-
Set the logging level. DEBUG can be used for additional logs.
ptp4lClockClassLockedList
-
Set the list of clock classes that will allow
ptp-notification
to report Locked. The clockClass for a monitored ptp4l instance is read via the . If the instance clockClass matches one of theptp4lClockClassLockedList
values, thenptp-notification
will report Locked for that instance.The default values are "6,7,135", which means that
ptp-notification
will report locked when reading a clockClass of 6, 7 or 135 from the configured ptp4l instance. These values are recommended for nodes operating as Boundary Clock (BC).For nodes operating as , it is recommended to set the value to "6", so that only clockClass 6 is reported as locked.
phc2sysToleranceThreshold
-
Default value: 1000
Set the skew threshold in nanoseconds at which
ptp-notification
will report that the system clock is no longer considered Locked.The
ptp-notification
application compares the time of the system clock to the configured source PHC. If the delta between the system clock and the is greater than thephc2sysToleranceThreshold
, a notification will be generated that the system clock is not locked. control_timeout: 2
-
control_timeout sets how frequently, in seconds the services are checked. Value applies to all service types.
device
-
device
refers to ptp4l monitoringholdover_seconds: 15
poll_freq_seconds: 2
osclock
-
holdover_seconds: 15
overall
-
- holdover_seconds: 15
-
holdover_seconds
configures how long each service will stay in the HOLDOVER state before transitioning to FREERUN. The holdover value used by the application equates to: holdover_seconds - (control_timeout * 2).This is done in order to account for time between the monitor polling cycles. The
holdover_seconds
value should be configured to match the validated holdover time provided by the device manufacturer.
View existing values.
~(keystone_admin)]$ system helm-override-show ptp-notification ptp-notification notification
Update and apply the values.
Application values can be added by the user and applied, using the following commands.
Note
Changes to the
ptp-notification
override values require the application to be removed and re-applied in order to re-create the application containers.~(keystone_admin)]$ system application-remove ptp-notification ~(keystone_admin)]$ system helm-override-update ptp-notification ptp-notification notification -–values <notification-override.yaml> ~(keystone_admin)]$ system application-apply ptp-notification
Verify the Helm overrides.
~(keystone_admin)]$ system helm-override-show ptp-notification ptp-notification notification
Apply
ptp-notification
using the command below.~(keystone_admin)]$ system application-apply ptp-notification
Verify application status and pod status using the following commands:
Application Status
~(keystone_admin)]$ system application-list
Pod Status
~(keystone_admin)]$ kubectl get pods -n notification -o wide
Configure Liveness Probes for PTP Notification Pods
Helm overrides can be used to configure liveness probes for the
following ptp-notification
containers:
- locationservice-base
- notificationservice-base
- notificationservice-base-v2
To enable the liveness probe for each container, include the following in the notification-override.yaml file:
location:
endpoint:
port: 8080
liveness: True
livenessDelaySeconds: 60
livenessPeriodSeconds: 3
livenessFailureThreshold: 3
livenessTimeoutSeconds: 3
ptptracking:
endpoint:
port: 8081
liveness: True
livenessDelaySeconds: 60
livenessPeriodSeconds: 3
livenessFailureThreshold: 3
livenessTimeoutSeconds: 3
ptptrackingv2:
endpoint:
port: 8082
liveness: True
livenessDelaySeconds: 60
livenessPeriodSeconds: 3
livenessFailureThreshold: 3
livenessTimeoutSeconds: 3
Apply the override values using the following commands:
~(keystone_admin)]$ system helm-override-update ptp-notification ptp-notification notification --values <notification-override.yaml>
~(keystone_admin)]$ system application-apply ptp-notification
supports applications that rely on PTP for synchronization. These applications are able to receive PTP status notifications from hosting the application. For more information see:
PTP Notifications Overview <ptp-notifications-overview>
- API PTP Notifications