SNMP driver
===========
The SNMP hardware type enables control of power distribution units of the type
frequently found in data centre racks. PDUs frequently have a management
ethernet interface and SNMP support enabling control of the power outlets.
The SNMP power interface works with the :ref:`pxe-boot` interface for network
deployment and network-configured boot.
.. note::
Unlike most of the other power interfaces, the SNMP power interface does
not have a corresponding management interface. The SNMP hardware type uses
the ``noop`` management interface instead.
List of supported devices
=========================
This is a non-exhaustive list of supported devices. Any device not listed in
this table could possibly work using a similar driver.
Please report any device status.
============== ========== ========== =====================
Manufacturer Model Supported? Driver name
============== ========== ========== =====================
APC AP7920 Yes apc_masterswitch
APC AP9606 Yes apc_masterswitch
APC AP9225 Yes apc_masterswitchplus
APC AP7155 Yes apc_rackpdu
APC AP7900 Yes apc_rackpdu
APC AP7901 Yes apc_rackpdu
APC AP7902 Yes apc_rackpdu
APC AP7911a Yes apc_rackpdu
APC AP7921 Yes apc_rackpdu
APC AP7922 Yes apc_rackpdu
APC AP7930 Yes apc_rackpdu
APC AP7931 Yes apc_rackpdu
APC AP7932 Yes apc_rackpdu
APC AP7940 Yes apc_rackpdu
APC AP7941 Yes apc_rackpdu
APC AP7951 Yes apc_rackpdu
APC AP7960 Yes apc_rackpdu
APC AP7990 Yes apc_rackpdu
APC AP7998 Yes apc_rackpdu
APC AP8941 Yes apc_rackpdu
APC AP8953 Yes apc_rackpdu
APC AP8959 Yes apc_rackpdu
APC AP8961 Yes apc_rackpdu
APC AP8965 Yes apc_rackpdu
Aten all? Yes aten
CyberPower all? Untested cyberpower
EatonPower all? Untested eatonpower
Teltronix all? Yes teltronix
BayTech MRP27 Yes baytech_mrp27
============== ========== ========== =====================
Software Requirements
=====================
- The PySNMP package must be installed, variously referred to as ``pysnmp``
or ``python-pysnmp``
Enabling the SNMP Hardware Type
===============================
#. Add ``snmp`` to the list of ``enabled_hardware_types`` in ``ironic.conf``.
Also update ``enabled_management_interfaces`` and
``enabled_power_interfaces`` in ``ironic.conf`` as shown below:
.. code-block:: ini
[DEFAULT]
enabled_hardware_types = snmp
enabled_management_interfaces = noop
enabled_power_interfaces = snmp
#. To set the default boot option, update ``default_boot_option`` in
``ironic.conf``:
.. code-block:: ini
[DEFAULT]
default_boot_option = netboot
.. note::
Currently the default value of ``default_boot_option`` is ``netboot``
but it will be changed to ``local`` in the future. It is recommended
to set an explicit value for this option.
.. note::
It is important to set ``boot_option`` to ``netboot`` as SNMP hardware
type does not support setting of boot devices. One can also configure
a node to boot using ``netboot`` by setting its ``capabilities`` and
updating Nova flavor as described below:
.. code-block:: console
openstack baremetal node set --property capabilities="boot_option:netboot" <node-uuid>
openstack flavor set --property "capabilities:boot_option"="netboot" ironic-flavor
#. Restart the Ironic conductor service.
.. code-block:: bash
service ironic-conductor restart
Ironic Node Configuration
=========================
Nodes configured to use the SNMP hardware type should have the ``driver`` field
set to the hardware type ``snmp``.
The following property values have to be added to the node's
``driver_info`` field:
- ``snmp_driver``: PDU manufacturer driver name or ``auto`` to automatically
choose ironic snmp driver based on ``SNMPv2-MIB::sysObjectID`` value as
reported by PDU.
- ``snmp_address``: the IPv4 address of the PDU controlling this node.
- ``snmp_port``: (optional) A non-standard UDP port to use for SNMP operations.
If not specified, the default port (161) is used.
- ``snmp_outlet``: The power outlet on the PDU (1-based indexing).
- ``snmp_version``: (optional) SNMP protocol version
(permitted values ``1``, ``2c`` or ``3``). If not specified, SNMPv1
is chosen.
- ``snmp_community``: (Required for SNMPv1/SNMPv2c unless
``snmp_community_read`` and/or ``snmp_community_write`` properties are
present in which case the latter take over) SNMP community
name parameter for reads and writes to the PDU.
- ``snmp_community_read``: SNMP community name parameter for reads
to the PDU. Takes precedence over the ``snmp_community`` property.
- ``snmp_community_write``: SNMP community name parameter for writes
to the PDU. Takes precedence over the ``snmp_community`` property.
- ``snmp_user``: (Required for SNMPv3) SNMPv3 User-based Security Model
(USM) user name. Synonym for now obsolete ``snmp_security`` parameter.
- ``snmp_auth_protocol``: SNMPv3 message authentication protocol ID.
Valid values include: ``none``, ``md5``, ``sha`` for all pysnmp versions
and additionally ``sha224``, ``sha256``, ``sha384``, ``sha512`` for
pysnmp versions 4.4.1 and later. Default is ``none`` unless ``snmp_auth_key``
is provided. In the latter case ``md5`` is the default.
- ``snmp_auth_key``: SNMPv3 message authentication key. Must be 8+
characters long. Required when message authentication is used.
- ``snmp_priv_protocol``: SNMPv3 message privacy (encryption) protocol ID.
Valid values include: ``none``, ``des``, ``3des``, ``aes``, ``aes192``,
``aes256`` for all pysnmp version and additionally ``aes192blmt``,
``aes256blmt`` for pysnmp versions 4.4.3+. Note that message privacy
requires using message authentication. Default is ``none`` unless
``snmp_priv_key`` is provided. In the latter case ``des`` is the default.
- ``snmp_priv_key``: SNMPv3 message privacy (encryption) key. Must be 8+
characters long. Required when message encryption is used.
- ``snmp_context_engine_id``: SNMPv3 context engine ID. Default is
the value of authoritative engine ID.
- ``snmp_context_name``: SNMPv3 context name. Default is an empty string.
The following command can be used to enroll a node with the ``snmp`` hardware
type:
.. code-block:: bash
openstack baremetal node create --os-baremetal-api-version=1.31 \
--driver snmp --driver-info snmp_driver=<pdu_manufacturer> \
--driver-info snmp_address=<ip_address> \
--driver-info snmp_outlet=<outlet_index> \
--driver-info snmp_community=<community_string> \
--properties capabilities=boot_option:netboot